Part Number Hot Search : 
RS804 71103 9152M 18634237 2000W 100PC 2J223J VCO55CL
Product Description
Full Text Search
 

To Download B84143-A36-R21 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 3-Line Filters for Converters and Power Electronics
Power line filters for three-phase systems Rated voltage 760/440 V~, 50/60 Hz Rated current 25 to 180 A Construction
s Three-line filter s Metal case
B84143-A*-R21
Features
s s s s s s
High insertion loss Low leakage current Easy to install Degree of protection: IP 20 1) Space-saving design Design based on EN 133200, UL 1283, CSA 22.2 No.8 1986 s Optimized for long motor cables and operation under full load Applications
s Frequency converters for motor drives, e.g.
- elevators - pumps - traction systems - conveyor systems - HVAC systems (heating, ventilation and air conditioning) s Wind farms s Power supplies Terminals
s Safe-to-touch terminal blocks
Marking Marking on component: Manufacturer's logo, ordering code, rated voltage, rated current, rated temperature, date code Minimum marking on packaging: Manufacturer's logo, ordering code
1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1
263 03/01
3-Line Filters for Converters and Power Electronics
Typical circuit diagram
B84143-A*-R21
LINE L1 L2 L3
LOAD L1' L2' L3'
SSB1189-I
Technical data Rated voltage V R Rated current I R Test voltage VP Overload capability Leakage current I leak Climatic category 760/440 V~, 50/60 Hz referred to 40 C ambient temperature 2121 V-, 2 s (line/line) 2700 V-, 2 s (lines/case) 1,5 * I R for 3 min per hour or 2,5 * I R for 30 s per hour at 690 V~, 50 Hz 25/1005/21 (- 25 C/+ 100 C/21 days damp heat test) in accordance with EN 60068-1
Characteristics and ordering codes IR A 25 36 50 80 120 150 180 I leak Terminal cross section mA mm2 10 10 10 25 50 50 95 Rtyp m 8,0 3,8 2,0 1,0 0,75 0,4 0,4 Approx. weight kg 4 4 4 9,5 10 10 13 Ordering code
<7 <7 < 12 < 12 < 12 < 12 < 12
B84143-A25-R21 B84143-A36-R21 B84143-A50-R21 B84143-A80-R21 B84143-A120-R21 B84143-A150-R21 B84143-A180-R21
264 03/01
3-Line Filters for Converters and Power Electronics
Dimensional drawings B84143-A25-R21 ... A50-R21
32+1
B84143-A*-R21
91 max.
650,4
12,50,4
PE M6 x 25 216 max. 800,2
22,51 1000,4 126 max.
4 x M6 6 tief 4 x M6/6/mmmm deep
LINE
LOAD
6,60,2 166 max.
Terminal blocks Anschlussklemmen 10 mm 10 mm 2 2
156 max.
L1 L2 L3 PE
1400,3
Marking
L1 L2 L3 PE
SSB1190-L
B84143-A80-R21
48,50,5
901
141 max.
10,1
PE M10 x 35 300 max. 1150,2
Marking Beschriftung
180,5 141 max.
L1 L2 L3 PE
LINE
LOAD
L1 L2 L3 PE
6,60,2 221 max.
Terminal blocks Anschlussklemmen 25 mm 25 mm 2 2
171 max.
1550,3
SSB1191-U
265 03/01
620,8
10,1
431
301
3-Line Filters for Converters and Power Electronics
B84143-A120-R21, B84143-A150-R21
540,5
B84143-A*-R21
971
141 max.
10,1
PE M10 x 35 348 max. 1150,2 141 max.
180,5
L1 L2 L3 PE
LINE
LOAD
6,60,2 261 max.
Anschlussklemmen Terminal blocks 50 mm 2 2 50 mm
1550,3
Marking
L1 L2 L3 PE
171 max.
SSB1192-3
B84143-A180-R21
1051
141 max.
740,5
650,8
10,1
PE M10 x 35 404 max. 301 max.
160,5 141 max.
L1 L2 L3 PE
Marking LINE LOAD
L1 L2 L3 PE
6,62,2 82,50,2 82,50,2
Anschlussklemmen Terminal blocks 2 95 mm 95 mm 2
SSB1193-B
266 03/01
171 max.
1550,3
620,8
3-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-A25-R21
100
SSB1194-J
B84143-A*-R21
B84143-A36-R21
100
SSB1195-S
e
dB 80
e
dB 80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7 f
Hz 10 8
0
10 4
10 5
10 6
10 7 f
Hz 10 8
B84143-A50-R21/B84143-A80-R21
100
SSB1196-1
B84143-A120-R21
100
SSB1197-9
e
dB 80
e
dB 80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7 f
Hz 10 8
0
10 4
10 5
10 6
10 7 f
Hz 10 8
267 03/01
3-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-A150-R21
100
SSB1198-H
B84143-A*-R21
B84143-A180-R21
100
SSB1199-Q
e
dB 80
e
dB 80
60
60
40
40
20
20
0 10 4
10 5
10 6
10 7 f
Hz 10 8
0
10 4
10 5
10 6
10 7
Hz 10 8 f
268 03/01
Herausgegeben von EPCOS AG Marketing Kommunikation, Postfach 80 17 09, 81617 Munchen, DEUTSCHLAND EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfaltigung, Veroffentlichung, Verbreitung und Verwertung dieser Broschure und ihres Inhalts ohne ausdruckliche Genehmigung der EPCOS AG nicht gestattet. Mit den Angaben in dieser Broschure werden die Bauelemente spezifiziert, keine Eigenschaften zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen fur Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird. Diese Broschure ersetzt die vorige Ausgabe. Fragen uber Technik, Preise und Liefermoglichkeiten richten Sie bitte an den Ihnen nachstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland. Bauelemente konnen aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskunfte daruber bitten wir unter Angabe des betreffenden Typs ebenfalls uber die zustandige Vertriebsgesellschaft einzuholen.
Published by EPCOS AG Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS' prior express consent is prohibited. The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless otherwise agreed. This brochure replaces the previous edition. For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or the international Representatives. Due to technical requirements components may contain dangerous substances. For information on the type in question please also contact one of our Sales Offices.
1


▲Up To Search▲   

 
Price & Availability of B84143-A36-R21

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X